Data series · Chapter 10

Scenario 3 — Pressure build-up and venting

Continued heating up to boiling. B4 switches in the first step after 2.8 bar is exceeded (t = 1470 s); after 120 s of venting the pressure is back at 0.0 bar.

Scenario
3 Pressure build-up
Expectation (criterion)
B4 when 2.8 bar is exceeded
Measurement
B4 in the first step thereafter (t = 1470.45 s); 0.0 bar after 120 s of venting
Result
passed
Rows
25,809
Time range
300.05–1,590.45 s
Time step
Δt = 0.05 s
Columns
9

Time series

Each quantity has its own axis and unit in its own panel; all share the time axis. The sensor bits appear as step lines. Clicking the legend shows or hides a quantity.

Time series of the measurement

Building the chart …

Quantities (click to show or hide)

    Controls: ← → move cursor (with ⇧ ten times) · Pos1 Ende to the edge · + − zoom · Bild↑ Bild↓ pan · 0 full series · Esc remove cursor. Drag a region with the mouse to zoom in. Values at the cursor belong to the nearest plotted data point; when zoomed far out the chart shows the minimum and maximum per pixel bucket so that single peaks stay visible. Exact values: zoom in or use the tables.

    Column description

    Name and unit come from the header row of the CSV file; the meaning follows the heated-tank model (chapter 8) and the recording (chapter 10).

    Columns of the series — Scenario 3 — Pressure build-up and venting
    No.Column (CSV header) UnitTypeMeaning
    1 Zeit (s) s Time axis Time stamp of the row (model time); one row per calculation step of Δt = 0.05 s.
    2 Füllstand (l) l Process variable Water level in the tank (tank volume 0.5 m³ = 500 l).
    3 Temperatur (°C) °C Process variable Water temperature, calculated from energy and water mass.
    4 Druck (bar) bar Process variable Pressure in the head space (steam and air, partial pressures added).
    5 Heizleistung (W) W Process variable Currently effective heating power (PT1 lag, τ = 12 s, up to 150 kW).
    6 B1 Füllstand max — Sensor bit (0/1) Upper level sensor: 1 from 450 l, otherwise 0.
    7 B2 Füllstand min — Sensor bit (0/1) Lower level sensor: 1 at 50 l or less, otherwise 0.
    8 B3 Temperatur ≥95 °C — Sensor bit (0/1) Temperature sensor: 1 from 95 °C, otherwise 0.
    9 B4 Druck ≥2,8 bar — Sensor bit (0/1) Pressure sensor: 1 from 2.8 bar, otherwise 0.

    Statistics of the series

    All figures are computed from the rows of the CSV file (over the whole series, without smoothing) and describe this single run only. They make no statement about a real tank.

    25,809Rows (calculation steps)
    1,290.45stime covered
    0.05sTime step Δt
    8recorded quantities
    Statistics per process variable — Scenario 3 — Pressure build-up and venting
    QuantityUnit CountMinimum MaximumMean First valueLast value
    Füllstand l 25,809 404.91t = 1,590.45 s 450.05t = 300.05 s 444.898 450.05 404.91
    Temperatur °C 25,809 39.572t = 300.05 s 122.732t = 1,470.40 s 87.1250 39.572 100.511
    Druck bar 25,809 0.0000t = 300.05 s 2.8048t = 1,470.45 s 0.3462 0.0000 0.0000
    Heizleistung W 25,809 150,000.0constant 150,000.0 150,000.00 150,000.0 150,000.0

    Below each extreme value is the time of the first row with that value. The mean is the simple mean over all rows (equal time steps).

    Sensor bits: switching times — Scenario 3 — Pressure build-up and venting
    Sensor bit Rows with 1 Share first 1 at then 0 again at Changes
    B1 Füllstand max 15,020 58.197 % 300.05 sfirst row 1,051.05 s 1
    B2 Füllstand min 0 0.000 % — — 0
    B3 Temperatur ≥95 °C 12,184 47.208 % 981.30 s — 1
    B4 Druck ≥2,8 bar 1 0.004 % 1,470.45 s 1,470.50 s 2

    1 means the sensor is active (threshold reached), 0 not active (chapter 8). “Changes” counts the rows in which the value differs from the previous row.

    Values

    All rows of the CSV file, unchanged, 100 rows per page. Search and sorting run on the server; you can jump to a row or a time. “No.” is a running row number and not part of the CSV.

    7,001–7,100 of 25,809 rows Download CSV
    Values — Scenario 3 — Pressure build-up and venting
    No. Zeit (s) Füllstand (l) Temperatur (°C) Druck (bar) Heizleistung (W) B1 Füllstand max B2 Füllstand min B3 Temperatur ≥95 °C B4 Druck ≥2,8 bar
    7,001 650.05450.0568.0490.0150000.01000
    7,002 650.1450.0568.0530.0150000.01000
    7,003 650.15450.0568.0570.0150000.01000
    7,004 650.2450.0568.0610.0150000.01000
    7,005 650.25450.0568.0650.0150000.01000
    7,006 650.3450.0568.0690.0150000.01000
    7,007 650.35450.0568.0740.0150000.01000
    7,008 650.4450.0568.0780.0150000.01000
    7,009 650.45450.0568.0820.0150000.01000
    7,010 650.5450.0568.0860.0150000.01000
    7,011 650.55450.0568.090.0150000.01000
    7,012 650.6450.0568.0940.0150000.01000
    7,013 650.65450.0568.0980.0150000.01000
    7,014 650.7450.0568.1020.0150000.01000
    7,015 650.75450.0568.1060.0150000.01000
    7,016 650.8450.0568.110.0150000.01000
    7,017 650.85450.0568.1140.0150000.01000
    7,018 650.9450.0568.1180.0150000.01000
    7,019 650.95450.0568.1220.0150000.01000
    7,020 651.0450.0568.1260.0150000.01000
    7,021 651.05450.0568.1310.0150000.01000
    7,022 651.1450.0568.1350.0150000.01000
    7,023 651.15450.0568.1390.0150000.01000
    7,024 651.2450.0568.1430.0150000.01000
    7,025 651.25450.0568.1470.0150000.01000
    7,026 651.3450.0568.1510.0150000.01000
    7,027 651.35450.0568.1550.0150000.01000
    7,028 651.4450.0568.1590.0150000.01000
    7,029 651.45450.0568.1630.0150000.01000
    7,030 651.5450.0568.1670.0150000.01000
    7,031 651.55450.0568.1710.0150000.01000
    7,032 651.6450.0568.1750.0150000.01000
    7,033 651.65450.0568.1790.0150000.01000
    7,034 651.7450.0568.1830.0150000.01000
    7,035 651.75450.0568.1870.0150000.01000
    7,036 651.8450.0568.1920.0150000.01000
    7,037 651.85450.0568.1960.0150000.01000
    7,038 651.9450.0568.20.0150000.01000
    7,039 651.95450.0568.2040.0150000.01000
    7,040 652.0450.0568.2080.0150000.01000
    7,041 652.05450.0568.2120.0150000.01000
    7,042 652.1450.0568.2160.0150000.01000
    7,043 652.15450.0568.220.0150000.01000
    7,044 652.2450.0568.2240.0150000.01000
    7,045 652.25450.0568.2280.0150000.01000
    7,046 652.3450.0568.2320.0150000.01000
    7,047 652.35450.0568.2360.0150000.01000
    7,048 652.4450.0568.240.0150000.01000
    7,049 652.45450.0568.2440.0150000.01000
    7,050 652.5450.0568.2480.0150000.01000
    7,051 652.55450.0568.2530.0150000.01000
    7,052 652.6450.0568.2570.0150000.01000
    7,053 652.65450.0568.2610.0150000.01000
    7,054 652.7450.0568.2650.0150000.01000
    7,055 652.75450.0568.2690.0150000.01000
    7,056 652.8450.0568.2730.0150000.01000
    7,057 652.85450.0568.2770.0150000.01000
    7,058 652.9450.0568.2810.0150000.01000
    7,059 652.95450.0568.2850.0150000.01000
    7,060 653.0450.0568.2890.0150000.01000
    7,061 653.05450.0568.2930.0150000.01000
    7,062 653.1450.0568.2970.0150000.01000
    7,063 653.15450.0568.3010.0150000.01000
    7,064 653.2450.0568.3050.0150000.01000
    7,065 653.25450.0568.310.0150000.01000
    7,066 653.3450.0568.3140.0150000.01000
    7,067 653.35450.0568.3180.0150000.01000
    7,068 653.4450.0568.3220.0150000.01000
    7,069 653.45450.0568.3260.0150000.01000
    7,070 653.5450.0568.330.0150000.01000
    7,071 653.55450.0568.3340.0150000.01000
    7,072 653.6450.0568.3380.0150000.01000
    7,073 653.65450.0568.3420.0150000.01000
    7,074 653.7450.0568.3460.0150000.01000
    7,075 653.75450.0568.350.0150000.01000
    7,076 653.8450.0568.3540.0150000.01000
    7,077 653.85450.0568.3580.0150000.01000
    7,078 653.9450.0568.3620.0150000.01000
    7,079 653.95450.0568.3660.0150000.01000
    7,080 654.0450.0568.3710.0150000.01000
    7,081 654.05450.0568.3750.0150000.01000
    7,082 654.1450.0568.3790.0150000.01000
    7,083 654.15450.0568.3830.0150000.01000
    7,084 654.2450.0568.3870.0150000.01000
    7,085 654.25450.0568.3910.0150000.01000
    7,086 654.3450.0568.3950.0150000.01000
    7,087 654.35450.0568.3990.0150000.01000
    7,088 654.4450.0568.4030.0150000.01000
    7,089 654.45450.0568.4070.0150000.01000
    7,090 654.5450.0568.4110.0150000.01000
    7,091 654.55450.0568.4150.0150000.01000
    7,092 654.6450.0568.4190.0150000.01000
    7,093 654.65450.0568.4230.0150000.01000
    7,094 654.7450.0568.4270.0150000.01000
    7,095 654.75450.0568.4320.0150000.01000
    7,096 654.8450.0568.4360.0150000.01000
    7,097 654.85450.0568.440.0150000.01000
    7,098 654.9450.0568.4440.0150000.01000
    7,099 654.95450.0568.4480.0150000.01000
    7,100 655.0450.0568.4520.0150000.01000

    Source and citation

    Data source: Own measurement series, recorded on the model function compute_step (step size Δt = 0.05 s) according to the test log of the bachelor thesis (2026); set-up and evaluation see Chapter 10 — Five test scenarios.

    How to cite

    Kotsch, A. H. (2026): Dataset „Scenario 3 — Pressure build-up and venting“ (25,809 rows, time 300.05–1,590.45 s). Supplement to the bachelor thesis „Digital twins for PLC-coupled laboratory systems“, Duale Hochschule Sachsen — Studienakademie Glauchau. https://thesis.kotsch.tech/daten/szenario-3-druckaufbau (accessed 2026-10-01).

    Limits of this data
    • Classification (chapter 10): B4 is set in exactly the step in which the threshold is exceeded.
    • Limit: The calculated pressure follows a sawtooth pattern; the threshold is exceeded by a single pressure peak, and the moment depends on the fluctuation band. In twelve rows (from t = 1051.05 s) the level, rounded to 0.01 l, is 450.0 l while B1 is already 0; this is compatible with the rounding of the recording.
    • The expected values come from hand calculation and the analytical solution with the parameters of the model; agreement shows the correct implementation, not the accuracy compared with a real tank. Each scenario covers a single run with fixed boundary conditions. (Chapter 10)
    • Without measurement data from a real tank, validation is limited to internal consistency. (Chapter 11)