Data series · Chapter 10

Scenario 1 — Filling

Inflow via Y1 and Y2, expected rise 2.55 l/s. Measurement: 2.551 l/s, B1 reports at 136.5 s.

Scenario
1 Filling
Expectation (criterion)
rise 2.55 l/s
Measurement
2.551 l/s; B1 at 136.5 s
Result
passed
Rows
3,000
Time range
0.05–150.00 s
Time step
Δt = 0.05 s
Columns
9

Time series

Each quantity has its own axis and unit in its own panel; all share the time axis. The sensor bits appear as step lines. Clicking the legend shows or hides a quantity.

Time series of the measurement

Building the chart …

Quantities (click to show or hide)

    Controls: ← → move cursor (with ⇧ ten times) · Pos1 Ende to the edge · + − zoom · Bild↑ Bild↓ pan · 0 full series · Esc remove cursor. Drag a region with the mouse to zoom in. Values at the cursor belong to the nearest plotted data point; when zoomed far out the chart shows the minimum and maximum per pixel bucket so that single peaks stay visible. Exact values: zoom in or use the tables.

    Column description

    Name and unit come from the header row of the CSV file; the meaning follows the heated-tank model (chapter 8) and the recording (chapter 10).

    Columns of the series — Scenario 1 — Filling
    No.Column (CSV header) UnitTypeMeaning
    1 Zeit (s) s Time axis Time stamp of the row (model time); one row per calculation step of Δt = 0.05 s.
    2 Füllstand (l) l Process variable Water level in the tank (tank volume 0.5 m³ = 500 l).
    3 Temperatur (°C) °C Process variable Water temperature, calculated from energy and water mass.
    4 Druck (bar) bar Process variable Pressure in the head space (steam and air, partial pressures added).
    5 Heizleistung (W) W Process variable Currently effective heating power (PT1 lag, τ = 12 s, up to 150 kW).
    6 B1 Füllstand max — Sensor bit (0/1) Upper level sensor: 1 from 450 l, otherwise 0.
    7 B2 Füllstand min — Sensor bit (0/1) Lower level sensor: 1 at 50 l or less, otherwise 0.
    8 B3 Temperatur ≥95 °C — Sensor bit (0/1) Temperature sensor: 1 from 95 °C, otherwise 0.
    9 B4 Druck ≥2,8 bar — Sensor bit (0/1) Pressure sensor: 1 from 2.8 bar, otherwise 0.

    Statistics of the series

    All figures are computed from the rows of the CSV file (over the whole series, without smoothing) and describe this single run only. They make no statement about a real tank.

    3,000Rows (calculation steps)
    150.00stime covered
    0.05sTime step Δt
    8recorded quantities
    Statistics per process variable — Scenario 1 — Filling
    QuantityUnit CountMinimum MaximumMean First valueLast value
    Füllstand l 3,000 101.96t = 0.05 s 484.49t = 150.00 s 293.227 101.96 484.49
    Temperatur °C 3,000 16.051t = 149.95 s 19.994t = 0.05 s 17.0748 19.994 16.051
    Druck bar 3,000 0.0000t = 148.35 s 0.0099t = 141.60 s 0.0094 0.0081 0.0000
    Heizleistung W 3,000 0.0constant 0.0 0.00 0.0 0.0

    Below each extreme value is the time of the first row with that value. The mean is the simple mean over all rows (equal time steps).

    Sensor bits: switching times — Scenario 1 — Filling
    Sensor bit Rows with 1 Share first 1 at then 0 again at Changes
    B1 Füllstand max 271 9.033 % 136.50 s — 1
    B2 Füllstand min 0 0.000 % — — 0
    B3 Temperatur ≥95 °C 0 0.000 % — — 0
    B4 Druck ≥2,8 bar 0 0.000 % — — 0

    1 means the sensor is active (threshold reached), 0 not active (chapter 8). “Changes” counts the rows in which the value differs from the previous row.

    Values

    All rows of the CSV file, unchanged, 100 rows per page. Search and sorting run on the server; you can jump to a row or a time. “No.” is a running row number and not part of the CSV.

    101–200 of 3,000 rows Download CSV
    Values — Scenario 1 — Filling
    No. Zeit (s) Füllstand (l) Temperatur (°C) Druck (bar) Heizleistung (W) B1 Füllstand max B2 Füllstand min B3 Temperatur ≥95 °C B4 Druck ≥2,8 bar
    101 5.05114.7219.4390.00850.00000
    102 5.1114.8519.4340.00850.00000
    103 5.15114.9719.4290.00850.00000
    104 5.2115.119.4240.00850.00000
    105 5.25115.2319.4190.00850.00000
    106 5.3115.3619.4140.00850.00000
    107 5.35115.4819.4090.00850.00000
    108 5.4115.6119.4040.00850.00000
    109 5.45115.7419.3990.00850.00000
    110 5.5115.8719.3950.00850.00000
    111 5.55115.9919.390.00850.00000
    112 5.6116.1219.3850.00850.00000
    113 5.65116.2519.380.00850.00000
    114 5.7116.3819.3750.00850.00000
    115 5.75116.5119.370.00850.00000
    116 5.8116.6319.3660.00850.00000
    117 5.85116.7619.3610.00850.00000
    118 5.9116.8919.3560.00850.00000
    119 5.95117.0219.3510.00850.00000
    120 6.0117.1419.3470.00850.00000
    121 6.05117.2719.3420.00850.00000
    122 6.1117.419.3370.00850.00000
    123 6.15117.5319.3330.00850.00000
    124 6.2117.6519.3280.00850.00000
    125 6.25117.7819.3230.00860.00000
    126 6.3117.9119.3180.00860.00000
    127 6.35118.0419.3140.00860.00000
    128 6.4118.1619.3090.00860.00000
    129 6.45118.2919.3050.00860.00000
    130 6.5118.4219.30.00860.00000
    131 6.55118.5519.2950.00860.00000
    132 6.6118.6719.2910.00860.00000
    133 6.65118.819.2860.00860.00000
    134 6.7118.9319.2810.00860.00000
    135 6.75119.0619.2770.00860.00000
    136 6.8119.1819.2720.00860.00000
    137 6.85119.3119.2680.00860.00000
    138 6.9119.4419.2630.00860.00000
    139 6.95119.5719.2590.00860.00000
    140 7.0119.6919.2540.00860.00000
    141 7.05119.8219.250.00860.00000
    142 7.1119.9519.2450.00860.00000
    143 7.15120.0819.240.00860.00000
    144 7.2120.219.2360.00860.00000
    145 7.25120.3319.2320.00860.00000
    146 7.3120.4619.2270.00860.00000
    147 7.35120.5919.2230.00860.00000
    148 7.4120.7119.2180.00860.00000
    149 7.45120.8419.2140.00860.00000
    150 7.5120.9719.2090.00860.00000
    151 7.55121.119.2050.00860.00000
    152 7.6121.2219.20.00860.00000
    153 7.65121.3519.1960.00860.00000
    154 7.7121.4819.1920.00860.00000
    155 7.75121.6119.1870.00860.00000
    156 7.8121.7319.1830.00860.00000
    157 7.85121.8619.1780.00860.00000
    158 7.9121.9919.1740.00860.00000
    159 7.95122.1219.170.00870.00000
    160 8.0122.2419.1650.00870.00000
    161 8.05122.3719.1610.00870.00000
    162 8.1122.519.1570.00870.00000
    163 8.15122.6319.1520.00870.00000
    164 8.2122.7619.1480.00870.00000
    165 8.25122.8819.1440.00870.00000
    166 8.3123.0119.1390.00870.00000
    167 8.35123.1419.1350.00870.00000
    168 8.4123.2719.1310.00870.00000
    169 8.45123.3919.1270.00870.00000
    170 8.5123.5219.1220.00870.00000
    171 8.55123.6519.1180.00870.00000
    172 8.6123.7819.1140.00870.00000
    173 8.65123.919.110.00870.00000
    174 8.7124.0319.1050.00870.00000
    175 8.75124.1619.1010.00870.00000
    176 8.8124.2919.0970.00870.00000
    177 8.85124.4119.0930.00870.00000
    178 8.9124.5419.0880.00870.00000
    179 8.95124.6719.0840.00870.00000
    180 9.0124.819.080.00870.00000
    181 9.05124.9219.0760.00870.00000
    182 9.1125.0519.0720.00870.00000
    183 9.15125.1819.0680.00870.00000
    184 9.2125.3119.0640.00870.00000
    185 9.25125.4319.0590.00870.00000
    186 9.3125.5619.0550.00870.00000
    187 9.35125.6919.0510.00870.00000
    188 9.4125.8219.0470.00870.00000
    189 9.45125.9419.0430.00870.00000
    190 9.5126.0719.0390.00870.00000
    191 9.55126.219.0350.00870.00000
    192 9.6126.3319.0310.00870.00000
    193 9.65126.4519.0270.00870.00000
    194 9.7126.5819.0230.00870.00000
    195 9.75126.7119.0190.00870.00000
    196 9.8126.8419.0140.00870.00000
    197 9.85126.9619.010.00880.00000
    198 9.9127.0919.0060.00880.00000
    199 9.95127.2219.0020.00880.00000
    200 10.0127.3518.9980.00880.00000

    Source and citation

    Data source: Own measurement series, recorded on the model function compute_step (step size Δt = 0.05 s) according to the test log of the bachelor thesis (2026); set-up and evaluation see Chapter 10 — Five test scenarios.

    How to cite

    Kotsch, A. H. (2026): Dataset „Scenario 1 — Filling“ (3,000 rows, time 0.05–150.00 s). Supplement to the bachelor thesis „Digital twins for PLC-coupled laboratory systems“, Duale Hochschule Sachsen — Studienakademie Glauchau. https://thesis.kotsch.tech/daten/szenario-1-befuellung (accessed 2026-11-14).

    Limits of this data
    • Classification (chapter 10): Direction and order of magnitude agree; B1 switches when 450 l is reached.
    • The expected values come from hand calculation and the analytical solution with the parameters of the model; agreement shows the correct implementation, not the accuracy compared with a real tank. Each scenario covers a single run with fixed boundary conditions. (Chapter 10)
    • Without measurement data from a real tank, validation is limited to internal consistency. (Chapter 11)