Data series · Chapter 10

Scenario 5 — Edge case: empty tank

Heating command on an empty tank: 1200 steps without runtime error, B1 = 0 and B2 = 1 throughout.

Scenario
5 Edge case: empty tank
Expectation (criterion)
no runtime error, no exception
Measurement
1200 steps without runtime error; B1 = 0, B2 = 1
Result
passed
Rows
1,200
Time range
0.05–60.00 s
Time step
Δt = 0.05 s
Columns
9

Time series

Each quantity has its own axis and unit in its own panel; all share the time axis. The sensor bits appear as step lines. Clicking the legend shows or hides a quantity.

Time series of the measurement

Building the chart …

Quantities (click to show or hide)

    Controls: ← → move cursor (with ⇧ ten times) · Pos1 Ende to the edge · + − zoom · Bild↑ Bild↓ pan · 0 full series · Esc remove cursor. Drag a region with the mouse to zoom in. Values at the cursor belong to the nearest plotted data point; when zoomed far out the chart shows the minimum and maximum per pixel bucket so that single peaks stay visible. Exact values: zoom in or use the tables.

    Column description

    Name and unit come from the header row of the CSV file; the meaning follows the heated-tank model (chapter 8) and the recording (chapter 10).

    Columns of the series — Scenario 5 — Edge case: empty tank
    No.Column (CSV header) UnitTypeMeaning
    1 Zeit (s) s Time axis Time stamp of the row (model time); one row per calculation step of Δt = 0.05 s.
    2 Füllstand (l) l Process variable Water level in the tank (tank volume 0.5 m³ = 500 l).
    3 Temperatur (°C) °C Process variable Water temperature, calculated from energy and water mass.
    4 Druck (bar) bar Process variable Pressure in the head space (steam and air, partial pressures added).
    5 Heizleistung (W) W Process variable Currently effective heating power (PT1 lag, τ = 12 s, up to 150 kW).
    6 B1 Füllstand max — Sensor bit (0/1) Upper level sensor: 1 from 450 l, otherwise 0.
    7 B2 Füllstand min — Sensor bit (0/1) Lower level sensor: 1 at 50 l or less, otherwise 0.
    8 B3 Temperatur ≥95 °C — Sensor bit (0/1) Temperature sensor: 1 from 95 °C, otherwise 0.
    9 B4 Druck ≥2,8 bar — Sensor bit (0/1) Pressure sensor: 1 from 2.8 bar, otherwise 0.

    Statistics of the series

    All figures are computed from the rows of the CSV file (over the whole series, without smoothing) and describe this single run only. They make no statement about a real tank.

    1,200Rows (calculation steps)
    60.00stime covered
    0.05sTime step Δt
    8recorded quantities
    Statistics per process variable — Scenario 5 — Edge case: empty tank
    QuantityUnit CountMinimum MaximumMean First valueLast value
    Füllstand l 1,200 0.0constant 0.0 0.00 0.0 0.0
    Temperatur °C 1,200 0.0constant 0.0 0.00 0.0 0.0
    Druck bar 1,200 0.0constant 0.0 0.00 0.0 0.0
    Heizleistung W 1,200 0.0constant 0.0 0.00 0.0 0.0

    Below each extreme value is the time of the first row with that value. The mean is the simple mean over all rows (equal time steps).

    Sensor bits: switching times — Scenario 5 — Edge case: empty tank
    Sensor bit Rows with 1 Share first 1 at then 0 again at Changes
    B1 Füllstand max 0 0.000 % — — 0
    B2 Füllstand min 1,200 100.000 % 0.05 sfirst row — 0
    B3 Temperatur ≥95 °C 0 0.000 % — — 0
    B4 Druck ≥2,8 bar 0 0.000 % — — 0

    1 means the sensor is active (threshold reached), 0 not active (chapter 8). “Changes” counts the rows in which the value differs from the previous row.

    Values

    All rows of the CSV file, unchanged, 100 rows per page. Search and sorting run on the server; you can jump to a row or a time. “No.” is a running row number and not part of the CSV.

    901–1,000 of 1,200 rows Download CSV
    Values — Scenario 5 — Edge case: empty tank
    No. Zeit (s) Füllstand (l) Temperatur (°C) Druck (bar) Heizleistung (W) B1 Füllstand max B2 Füllstand min B3 Temperatur ≥95 °C B4 Druck ≥2,8 bar
    901 45.050.0-0.00.00.00100
    902 45.10.0-0.00.00.00100
    903 45.150.0-0.00.00.00100
    904 45.20.0-0.00.00.00100
    905 45.250.0-0.00.00.00100
    906 45.30.0-0.00.00.00100
    907 45.350.0-0.00.00.00100
    908 45.40.0-0.00.00.00100
    909 45.450.0-0.00.00.00100
    910 45.50.0-0.00.00.00100
    911 45.550.0-0.00.00.00100
    912 45.60.0-0.00.00.00100
    913 45.650.0-0.00.00.00100
    914 45.70.0-0.00.00.00100
    915 45.750.0-0.00.00.00100
    916 45.80.0-0.00.00.00100
    917 45.850.0-0.00.00.00100
    918 45.90.0-0.00.00.00100
    919 45.950.0-0.00.00.00100
    920 46.00.0-0.00.00.00100
    921 46.050.0-0.00.00.00100
    922 46.10.0-0.00.00.00100
    923 46.150.0-0.00.00.00100
    924 46.20.0-0.00.00.00100
    925 46.250.0-0.00.00.00100
    926 46.30.0-0.00.00.00100
    927 46.350.0-0.00.00.00100
    928 46.40.0-0.00.00.00100
    929 46.450.0-0.00.00.00100
    930 46.50.0-0.00.00.00100
    931 46.550.0-0.00.00.00100
    932 46.60.0-0.00.00.00100
    933 46.650.0-0.00.00.00100
    934 46.70.0-0.00.00.00100
    935 46.750.0-0.00.00.00100
    936 46.80.0-0.00.00.00100
    937 46.850.0-0.00.00.00100
    938 46.90.0-0.00.00.00100
    939 46.950.0-0.00.00.00100
    940 47.00.0-0.00.00.00100
    941 47.050.0-0.00.00.00100
    942 47.10.0-0.00.00.00100
    943 47.150.0-0.00.00.00100
    944 47.20.0-0.00.00.00100
    945 47.250.0-0.00.00.00100
    946 47.30.0-0.00.00.00100
    947 47.350.0-0.00.00.00100
    948 47.40.0-0.00.00.00100
    949 47.450.0-0.00.00.00100
    950 47.50.0-0.00.00.00100
    951 47.550.0-0.00.00.00100
    952 47.60.0-0.00.00.00100
    953 47.650.0-0.00.00.00100
    954 47.70.0-0.00.00.00100
    955 47.750.0-0.00.00.00100
    956 47.80.0-0.00.00.00100
    957 47.850.0-0.00.00.00100
    958 47.90.0-0.00.00.00100
    959 47.950.0-0.00.00.00100
    960 48.00.0-0.00.00.00100
    961 48.050.0-0.00.00.00100
    962 48.10.0-0.00.00.00100
    963 48.150.0-0.00.00.00100
    964 48.20.0-0.00.00.00100
    965 48.250.0-0.00.00.00100
    966 48.30.0-0.00.00.00100
    967 48.350.0-0.00.00.00100
    968 48.40.0-0.00.00.00100
    969 48.450.0-0.00.00.00100
    970 48.50.0-0.00.00.00100
    971 48.550.0-0.00.00.00100
    972 48.60.0-0.00.00.00100
    973 48.650.0-0.00.00.00100
    974 48.70.0-0.00.00.00100
    975 48.750.0-0.00.00.00100
    976 48.80.0-0.00.00.00100
    977 48.850.0-0.00.00.00100
    978 48.90.0-0.00.00.00100
    979 48.950.0-0.00.00.00100
    980 49.00.0-0.00.00.00100
    981 49.050.0-0.00.00.00100
    982 49.10.0-0.00.00.00100
    983 49.150.0-0.00.00.00100
    984 49.20.0-0.00.00.00100
    985 49.250.0-0.00.00.00100
    986 49.30.0-0.00.00.00100
    987 49.350.0-0.00.00.00100
    988 49.40.0-0.00.00.00100
    989 49.450.0-0.00.00.00100
    990 49.50.0-0.00.00.00100
    991 49.550.0-0.00.00.00100
    992 49.60.0-0.00.00.00100
    993 49.650.0-0.00.00.00100
    994 49.70.0-0.00.00.00100
    995 49.750.0-0.00.00.00100
    996 49.80.0-0.00.00.00100
    997 49.850.0-0.00.00.00100
    998 49.90.0-0.00.00.00100
    999 49.950.0-0.00.00.00100
    1,000 50.00.0-0.00.00.00100

    Source and citation

    Data source: Own measurement series, recorded on the model function compute_step (step size Δt = 0.05 s) according to the test log of the bachelor thesis (2026); set-up and evaluation see Chapter 10 — Five test scenarios.

    How to cite

    Kotsch, A. H. (2026): Dataset „Scenario 5 — Edge case: empty tank“ (1,200 rows, time 0.05–60.00 s). Supplement to the bachelor thesis „Digital twins for PLC-coupled laboratory systems“, Duale Hochschule Sachsen — Studienakademie Glauchau. https://thesis.kotsch.tech/daten/szenario-5-grenzfall (accessed 2026-11-14).

    Limits of this data
    • Classification (chapter 10): The model handles the edge case without aborting; the criterion is the absence of an error.
    • Limit: The published series contains only model quantities and sensor bits; the absence of a runtime error is documented in the test log, not in the rows.
    • The expected values come from hand calculation and the analytical solution with the parameters of the model; agreement shows the correct implementation, not the accuracy compared with a real tank. Each scenario covers a single run with fixed boundary conditions. (Chapter 10)
    • Without measurement data from a real tank, validation is limited to internal consistency. (Chapter 11)

    More datasets